Multistage Centrifugal High Pressure Stainless Steel Jockey Pump Fire Water Pump

Short Description:

Model No:GDL

GDL Vertical fire Pump with control panel is the latest model, energy-saving, less space demand, easy to install and stable performance.(1) With its 304 stainless steel shell and wear-resistant axle seal, it is no leakage and long service life.(2) With hydraulic equilibrium to balance the axial force, the pump can run more smoothly, less noise and, which can be easily installed in the pipeline which is on the same level, enjoying better installation conditions than DL model.(3) With these features, GDL Pump can easily meet the needs and requirements for water supply and drain for high building, deep well and firefighting equipments.


Feature

Technical data

                    e3 Outlet Diameter 25-150 mm
Capacity 18-360 m3/h
Pressure 0.3-2.5MPa
Medium temperature -10 ~ 80°C
Material Casing/impeller: cast iron, stainless steel, copper, bronze, Shaft: carbon steel 45#,stainless steel
Seal Bergmann mechanical seal
Bearing SKF/NTN/NSK
Motor High quality motor or UL motor
Jockey pump Yes, can be fire-fighting type
scope of supply : Engine drive fire pump+ control panel+ Jockey pump                Electrical motor drive pump +  control panel+ Jockey pump
Other request for the unit please discuses with TKFLO engineers.

A jockey pump is a pump connected to a fire sprinkler system and is intended to maintain pressure in a fire protection piping system to an artificially high level so that the operation of a single fire sprinkler will cause a pressure drop which will be sensed by the fire pump automatic controller, causing the fire pump to start. The jockey pump is essentially a portion of the fire pump's control system.

e1

Quality Assurance Safety

NFPA20 Standard Firefighting Application Fire Jockey Pump
Fire Jockey Pump Introduction:

A jockey pump is sized for a flow less than the flow to one sprinkler in order to ensure a system pressure drop. Hence a jockey pump is an important part of the fire pumps control system. Jockey pumps are typically small multistage centrifugal pumps, and do not have to be listed or certified for fire system application. The control equipment for jockey pumps may however carry approvals.

Jockey pumps should be sized for 3% of the flow of the main fire pump and to provide 10psi more pressure than the main fire pump (As per Code IS 15105 : 2002) The application of a jockey pump in a fire protection system is provided by NFPA 20. They are inspected per NFPA 25 "Inspection and Testing of Water-Based Fire Protection Systems".

Product Structural Features & Performance Advantages

Stainless steel vertical multistage pump for fire fighting group
♦ No blocking during operation. The use of copper alloy water guide bearing and stainless steel pump shaft avoids rusty gripping at each tiny clearance, which is very important to fire-fighting system;
♦ No leakage. The adoption of high-quality mechanical seal ensures a clean working site;
♦ Low-noise and steady operation. The low-noise bearing is designed to come with precise hydraulic parts. The water-filled shield outside each subsection not only lowers flow noise, but also ensures steady operation;
♦ Easy installation and assembly. The pump's inlet and outlet diameters are same, and located on a straight line. Like valves, they may be directly mounted on the pipeline;
♦ The use of shell-type coupler not only simplifies the connection between pump and motor, but also enhances transmission efficiency.

Overview:
GDL Vertical fire Pump with control panel is the latest model, energy-saving, less space demand, easy to install and stable performance.

(1) With its 304 stainless steel shell and wear-resistant axle seal, it is no leakage and long service life.
(2) With hydraulic equilibrium to balance the axial force, the pump can run more smoothly, less noise and, which can be easily installed in the pipeline which is on the same level, enjoying better installation conditions than DL model.
(3) With these features, GDL Pump can easily meet the needs and requirements for water supply and drain foe high building, deep well and firefighting equipments.

e2

The TONGKE Pump Fire Pump Units, Systems, and Packaged Systems

TONGKE Fire Pump installations (UL approved ,Follow NFPA 20 and CCCF ) deliver superior fire protection to facilities worldwide. TONGKE Pump has been offering complete service, from engineering assistance to in house fabrication to field start-up. Products are designed from a broad selection of pumps, drives, controls, base plates and accessories. Pump choices include horizontal, in-line and end suction centrifugal fire pumps as well as vertical turbine pumps.

Both horizontal and vertical models provide capabilities up to 5,000 gpm. End suction models deliver capacities to 2,000 gpm. In-line units can produce 1,500 gpm. Head ranges from 100 ft to 1,600 ft with as much as 500 meters. Pumps are powered with electric motors, diesel engines or steam turbines. Standard fire pumps are Ductile cast iron with bronze fittings. TONGKE supply the fittings and accessories recommended by the NFPA 20.

Applications
Applications vary from small, basic electric motor driven to diesel engine driven, packaged systems. Standard units are designed to handle fresh water, but special materials are available for sea water and special liquid applications.
The TONGKE Fire Pumps give superior performance in Agriculture, General Industry, Building Trade, Power Industry, Fire Protection, Municipal, and Process applications. 

a3
a4

Fire Protection
You have decided to reduce the risk of fire damage to your facility by installing a UL, ULC listed fire pump system. Your next decision is which system to purchase.
You want a fire pump that is proven in installations worldwide. Manufactured by an professional with vast experience in the fire protection field. You want complete service to field start-up. You want a TONGKE Pump.

Providing Pumping Solutions TONGKE Can Fulfill Your Requirements:
● Complete in-house fabrication capabilities

● Mechanical-run test capabilities with customer furnished equipment for all NFPA standards
● Horizontal models for capacities to 2,500 gpm
● Vertical models for capacities to 5,000 gpm
● In-line models for capacities to 1,500 gpm
● End suction models for capacities to 1,500 gpm
● Drives: electric motor or diesel engine
● Basic units and packaged systems.

FRQ

Q. What makes a fire pump different from other kinds of pumps?
A.  First, they meet the stringent requirements of NFPA Pamphlet 20, Underwriters Laboratories and Factory Mutual Research Corporation for reliability and unfailing service under the most difficult and demanding circumstances. This fact alone should speak well for TKFLO's product quality and premium design features. Fire pumps are required to produce specific flow rates (GPM) and pressures of 40 PSI or greater. Further, the above mentioned agencies advise that the pumps should produce at least 65% of that pressure at 150% of the rated flow -- and all the while operating at a 15 foot lift condition. The performance curves must be such that the shut-off head, or "churn," is from 101% to 140% of the rated head, depending upon the agency's definition of the term. TKFLO's fire pumps are not offered for fire pump service unless they meet all agencies' requirements.

Beyond performance characteristics, TKFLO fire pumps are carefully scrutinized by both NFPA and F.M. for reliability and long life through analysis of their design and construction. Casing integrity, for example, must be suitable to withstand a hydrostatic test of three times the maximum operating pressure without bursting! TKFLO's compact and well-engineered design allows us to satisfy this specification with many of our 410 and 420 models. Engineering calculations for bearing life, bolt stress, shaft deflection, and shear stress must also be submitted to NFPA . and F.M. and must fall within conservative limits to ensure utmost reliability. Finally, after all the preliminary requirements have been met, the pump is ready for final certification testing to be witnessed by representatives from U.L. and F.M. Performance tests will require that several impeller diameters will be demonstrated satisfactorily, including the minimum and maximum, and several in between.

Q. What is the typical lead time for a fire pump?
A. Typical lead times run 5-8 weeks from release of an order. Call us for details. 

Q. What is the easiest way of determining pump rotation?
A. For a horizontal split-case fire pump, if you are sitting on the motor facing the fire pump, from this vantage point a pump is right-hand, or clock-wise, if the suction is coming from the right and the discharge is heading toward the left. The opposite is true for left-handed, or counter-clockwise rotation. The key is the vantage point when discussing this topic. Make sure both parties are viewing the pump casing from the same side.

Q. How are engines and motors sized for fire pumps?
A. Motors and engines supplied with TKFLO fire pumps are sized according to U.L., F.M. and NFPA 20 (2013), and are designed to operate on any point of the fire pump curve without exceeding the motor nameplate service factor, or engine size. Do not be fooled into thinking that the motors are sized only to 150% of nameplate capacity. It is not uncommon for fire pumps to operate well beyond 150% of rated capacity (for example, if there is an open hydrant or broken pipe downstream).

For more specifics, please refer to NFPA 20 (2013) paragraph 4.7.6, UL-448 paragraph 24.8, and Factory Mutual's Approval Standard for Split Case Fire Pumps, Class 1311, paragraph 4.1.2. All motors and engines supplied with TKFLO fire pumps are sized to the true intent of NFPA 20, U.L. , and Factory Mutual.
Since fire pump motors are not expected to be running continuously, they are often sized to take advantage of a 1.15 motor service factor. So unlike domestic water or HVAC pump applications, a fire pump motor is not always sized “non-overloading” across the curve. As long as you do not exceed the motor 1.15 service factor, it is allowed. An exception to this is when a variable speed inverter duty electric motor is used.

Q. Can I use a flow meter loop as a substitute for a test header?
A. A flow meter loop is often practical where flowing excessive water through standard U.L. Playpipe nozzles are inconvenient; however, when using a closed flow meter loop around a fire pump, you may be testing the pumps hydraulic performance, but you are NOT testing the water supply, which is a critical component of the fire pump system. If there is an obstruction to the water supply, this will not be evident with a flow meter loop, but will certainly be exposed by testing a fire pump with hoses and Playpipes. On an initial start-up of a fire pump system, we always insist on flowing water through the system to ensure the integrity of the entire system.

If a flow meter loop is returned back to the water supply -- such as an above-ground water tank -- then under that arrangement you will be able to test both the fire pump and the water supply. Just make sure that your flow meter is properly calibrated. 

Q. Do I need to worry about NPSH in fire pump applications?
A. Rarely. NPSH (net positive suction head) is an important consideration in industrial applications, such as boiler feed or hot water pumps. With fire pumps, however, you are dealing with cold water, which uses all of atmospheric pressure to your advantage. Fire pumps need a "flooded suction," where the water arrives to the pump impeller through gravity. You need this to guarantee a pump prime 100% of the time, so that when you have a fire, your pump operates! It is certainly possible to install a fire pump with a foot valve or some artificial means for priming, but there is no way to guarantee 100% that the pump will function properly when called on to operate. In many split-case double suction pumps, it only takes approximately 3% of air in the pump casing to render the pump inoperable. For that reason, you will not find a fire pump manufacturer willing to risk selling a fire pump for any installation that does not guarantee a "flooded suction" to the fire pump at all times.

Q. When will you answer more questions on this FAQ page?
A. We will add them as issues arise, but feel free to contact us with your questions!

Packing & Shipping
Packaging: Conventional Packaging suitable for by sea or long distance transportation.
Shipping: 20-45 working days after receiving the deposit of the devices
 
Quality guarantee
Shanghai Tongke flow technology Co., Ltd. always focus on the Technology design, The company's gist is different operation and the goal is the high-quality, high-performance products. We strive to become a trustworthy professional automobile seat cushion company. We passed the TUV resisted ISO 9001 and products is passed SGS inspection. Fire fighting Jockey Pump with control panel.

Services:
1.one year guarantee for whole machine except for wear parts;
2.24 hours technical support by email;
3.calling service;
4.user manual available;
5.reminding for the service life of the wearing parts;
6.installation guide for clients from both China and abroad;
7.maintance and replacement service;
8.whole process training and guidance from our technicians.

Applicant

Large hotels, hospitals , schools,office buildings,supermarkets, commercial residential buildings, metro stations, railway stations, airports, kinds of transportation tunnels, petrochemical plants, thermal power plants, terminals, oil depots, large warehouses and industrial and mining enterprises, etc.

A jockey pump is a small pump connected to a fire sprinkler system to maintain pressure in the sprinkler pipes. This is to ensure that if a fire-sprinkler is activated, there will be a pressure drop, which will be sensed by the fire pumps automatic controller, which will cause the fire pump to start.

A jockey pump is sized for a flow less than the flow to one sprinkler in order to ensure a system pressure drop. Hence a jockey pump is an important part of the fire pumps control system.

Jockey pumps are typically small multistage centrifugal pumps, and do not have to be listed or certified for fire system application. The control equipment for jockey pumps may however carry approvals.